| Power |
|---|
| Output voltage regulation | 1% |
| Output frequency regulation | 0.5 Hz |
| Output power factor | 0.95 |
| Input power factor | 0.99 |
| Output power | 3800 W |
| Input operation voltage (min) | 110 V |
| Input operation voltage (max) | 300 V |
| Output operation voltage (min) | 200 V |
| Output operation voltage (max) | 240 V |
| Surge energy rating | 1335 J |
| Maximum current | 20 A |
| Emergency Power Off (EPO) | Yes |
| Crest factor | 3:1 |
| Output power capacity | 4 kVA |
| Total Harmonic Distortion (THD) (linear load) | 1.5% |
| Total Harmonic Distortion (THD) (non-linear load) | 2% |
| Power Factor Correction (PFC) type | Active |
| Charging current | 4 A |
| Efficiency (ECO mode) | 98% |
| ECO mode | Yes |
| Ports & interfaces |
|---|
| Socket circuit breaker | Yes |
| Emergency Power Off (EPO) connector | Yes |
| USB port | Yes |
| Serial interface | Yes |
| Serial interface type | RS-232 |
| SmartSlot | Yes |
| AC outlets quantity | 15 AC outlet(s) |
| AC outlet types | C13 coupler, C19 coupler, Terminal |
| Power plug | Terminal |
| USB 2.0 ports quantity | 1 |
| Serial ports quantity | 3 |
| RS-232 ports | 3 |
| USB port type | USB Type-B |
| Performance |
|---|
| UPS topology | Double-conversion (Online) |
| Waveform | Pure sine |
| Number of output phases | 1 |
| Number of input phases | 1 |
| LED indicators | Yes |
| EMI/RFI noise filtering | Yes |
| Features |
|---|
| Output frequency | 50/60 Hz |
| Country of origin | China |
| UPS topology | Double-conversion (Online) |
| Waveform | Pure sine |
| Output voltage regulation | 1% |
| Output frequency regulation | 0.5 Hz |
| Number of output phases | 1 |
| Number of input phases | 1 |
| Output power factor | 0.95 |
| Input power factor | 0.99 |
| Output power | 3800 W |
| Input operation voltage (min) | 110 V |
| Input operation voltage (max) | 300 V |
| Output operation voltage (min) | 200 V |
| Output operation voltage (max) | 240 V |
| Surge energy rating | 1335 J |
| Maximum current | 20 A |
| EMI/RFI noise filtering | Yes |
| Emergency Power Off (EPO) | Yes |
| Crest factor | 3:1 |
| Output power capacity | 4 kVA |
| Total Harmonic Distortion (THD) (linear load) | 1.5% |
| Total Harmonic Distortion (THD) (non-linear load) | 2% |
| Power Factor Correction (PFC) type | Active |
| Socket circuit breaker | Yes |
| Efficiency (ECO mode) | 98% |
| ECO mode | Yes |
| Input frequency | 50/60 Hz |
| Power source type | AC |
| Detachable power cord | Yes |
| Heat dissipation | 1777 BTU/h |
| Package type | Box |
| Charging current | 4 A |
| Battery |
|---|
| Battery technology | Sealed Lead Acid (VRLA) |
| Battery recharge time | 4 h |
| Typical backup time at half load | 15 min |
| Typical backup time at full load | 6 min |
| Hot-swap battery | Yes |
| Charging current | 4 A |
| Design |
|---|
| Country of origin | China |
| Rack capacity | 4U |
| Form factor | Rackmount/Tower |
| LED indicators | Yes |
| Product colour | Black |
| Cooling type | Active |
| Built-in fan | Yes |
| Housing material | Metal |
| Control type | Buttons |
| Display type | LCD |
| Operational conditions |
|---|
| Operating temperature (T-T) | 0 - 40 °C |
| Storage temperature (T-T) | -15 - 45 °C |
| Operating relative humidity (H-H) | 0 - 95% |
| Storage relative humidity (H-H) | 0 - 95% |
| Operating altitude | 0 - 3000 m |
| Non-operating altitude | 0 - 15000 m |
| Technical details |
|---|
| Output frequency | 50/60 Hz |
| Quantity of delay expansion units (max) | 4 |
| Sustainability compliance | Yes |
| Compliance certificates | CE, RoHS |
| Cooling |
|---|
| Cooling type | Active |
| Built-in fan | Yes |
| Weight & dimensions |
|---|
| Package type | Box |
| Package width | 575 mm |
| Package depth | 890 mm |
| Package height | 404 mm |
| Weight | 55 kg |
| Width | 433 mm |
| Package weight | 73 kg |
| Height | 171 mm |
| Depth | 661 mm |
| Packaging data |
|---|
| Package type | Box |
| Package width | 575 mm |
| Package depth | 890 mm |
| Package height | 404 mm |
| Package weight | 73 kg |
| Other features |
|---|
| Overload protection | Yes |
| Nominal input voltage | 230 V |
| Quantity of delay expansion units (max) | 4 |